Karl  P.

Karl P.

HVAC Service call for a Lennox Packaged RTU. Preventative Maintenance service completed per contracted agreement. All requirements per seasonal obligations have been met. Any issues found during PM service have been brought to the attention of the appropriate personnel and have been defined as either a critical or a non-critical issue for their review. HVAC call is complete.

Near Quaker Ln, Warwick, RI 02886
Brian  C.

Brian C.

Walk-in cooler condenser replacement. Call is complete.

Near Universal Blvd, Warwick, RI 02886
Donald  G.

Donald G.

HVAC call. Arrived on site to find Kitchen Carrier RTU with condensation issues. Clear rust from pan and line entry. Resecured panel with new gasket. Call is complete.

Near Bald Hill Rd, Warwick, RI 02886
Scott  F.

Scott F.

HVAC Service call. Preventative Maintenance service completed per contracted agreement. All requirements per seasonal obligations have been met. Any issues found during PM service have been brought to the attention of the appropriate personnel and have been defined as either a critical or a noncritical issue for their review. HVAC call is complete.

Near Universal Blvd, Warwick, RI 02886
Brian  C.

Brian C.

HVAC Service call. Preventative Maintenance service completed per contracted agreement. All requirements per seasonal obligations have been met. Any issues found during PM service have been brought to the attention of the appropriate personnel and have been defined as either a critical or a non critical issue for their review. HVAC call is complete.

Near Bald Hill Rd, Warwick, RI 02886
Nathan  C.

Nathan C.

Ventilation call. Arrived on site and found that overnight cleaners had thrown power switch. Call is complete.

Near Bald Hill Rd, Warwick, RI 02886
Mark S.

Mark S.

Refrigeration Call. Found evaporator coil lately frozen. Unit is a Reach in refrigerator with heaters for defrost. Initiated defrost and confirmed amp draw from heaters. Manually thawed coil. Found defrost time clock timer not functioning, which is cause of ice build up. Removed and replaced time clock, chemically cleaned condenser coil. Ran unit and confirmed cycling at temperature upon leaving. Time clock does advance properly and defrost initiates properly. Call is complete.

Near Post Rd, Warwick, RI 02886
Scott  F.

Scott F.

HVAC Service call. Preventative Maintenance service completed per contracted agreement. All requirements per seasonal obligations have been met. Any issues found during PM service have been brought to the attention of the appropriate personnel and have been defined as either a critical or a non critical issue for their review. HVAC call is complete.

Near Bald Hill Rd, Warwick, RI 02886
Scott  F.

Scott F.

Ventilation call. Removed and replaced blowers motors, motor pulleys, crank case heaters, and motor tensioner assembly per quote. Tested operations. Call is complete.

Near Quaker Ln, Warwick, RI 02886
Scott  F.

Scott F.

HVAC Service call. Preventative Maintenance service completed per contracted agreement. All requirements per seasonal obligations have been met. Any issues found during PM service have been brought to the attention of the appropriate personnel and have been defined as either a critical or a non critical issue for their review. HVAC call is complete.

Near Bald Hill Rd, Warwick, RI 02886
Donald  G.

Donald G.

Customer reports that their reach-in cooler was not keeping temperature. - Recovered refrigerant to EPA specification. - Removed and replaced left and right solenoid valves . - Removed and replaced faulty TXVs. - Removed and replaced drier and sight glass. - Evacuated system to proper micron level - Charged to operating pressure. - Started and dialed in charge.Equipment is functional and working properly and the call is complete.

Near Bald Hill Rd, Warwick, RI 02886
Donald  G.

Donald G.

Exhaust over fryer not workingShut down exhaust. Picked up shop fabricated curb adapter and block off plates. Detached fan from existing curb. Installed block off plates to keep grease out from between duct and existing curb. Set new adapter in place and secured. Set fan on adapter, fan now sits firmly in place. Unit is operational- Call Complete

Near Post Rd, Warwick, RI 02888
Yanni F.

Yanni F.

Walk in Freezer running warm @ 75*Checked in with manager on arrival. Box temp warm and product defrosting. Found evap fully iced up. Accessed condenser and made mark on time clock to see if it was advancing. Forced unit into defrost and system continued in refrigeration. Tested defrost termination to find it had failed. Shut system down, disassembled evap and set up hose to melt ice with hot water. Replaced defrost clock as well. Restored power to system and tested operations. Assured clock was advancing properly, as well as kicking in and out of defrost cycles. Set up defrost cycles as previous clock was set up. Watched box temp drop but it will take time to satisfy due to all defrosted product in box.

Near Bald Hill Rd, Warwick, RI 02886